Intelligent System

I-9301

Addressable Single I/O Module

I-9301 Addressable Single I/O Module works in two-wire mode and four-wire mode. In four-wire mode, on receiving start command from the fire alarm control panel (FACP), it will close the output relay to output 24VDC and illuminate the Active indicator. If there is short, open circuit, or power down, the module can check failure and report it to the FACP.
In two-wire mode, on receiving start command from the fire alarm control panel (FACP), it will close the output relay to output normally-open normally close contact signal and illuminate the Active indicator.


Manufacturer: GST

PRICE: ₱ 5,188.56

Free Delivery within Metro Manila


Features

Two-wire and four-wire modes can be programmed through hand held programmer
Electronic address can be modified in field
Built-in MCU processes messages intelligently
Monitoring power supply
Fault and action indicators available
Four wire output cable checking
Plug-in structure.

Technical Data

Operating Voltage: Signal Loop 24V(16V~28V)
Power 24VDC(20VDC~28VDC)
Standby Current: Loop≤1mA ; Power≤5mA
Action Current: Loop≤3mA ; Power≤20mA
Output Capacity: Four-wire mode: 24VDC/1A
Two-wire mode: 24VDC/2A
Programming Method: Electronically programmed
Ingress Protection Rating: IP30
Code Range: One address within 1~242
Operating Temperature: -10℃~+55℃
Relative Humidity: ≤93%, non condensing
Material of Enclosure: ABS
Dimension: 120mm×80mm×43mm (with base)
Weight: About 194g (with base)